Tank location with respect to the
nearest important structure, building or group buildings should be
10 feet for 125-500 gallon water capacity tanks, 25 feet for
501-2,000 gallon water capacity tanks and 50 feet for 2,001-30,000
gallon water capacity tanks. (For multiple tanks, add the capacity
of the tanks together and use the appropriate distance.)
-
Equip the system with two stage
regulation. The first stage regulator should be at the tank,
the second stage regulator at the building.
-
Provide a concrete, masonry or other
firm foundation for tanks.
-
Loose or piled combustible material,
weeds, and long dry grass shall not be permitted within 10 feet of
any container.
-
Provided a cover for the tank
controls so their operation will not be affected by freezing rain,
sleet, snow, ice, or other material.
-
Equip all LP gas fired heating
equipment with a 100% automatic shut-off device in accordance with
he National Fire Protection Association's pamphlet #58-Storage and
Handling of Liquified Petroleum Gases.
-
Make sure all regulator vents are
pointing down.
-
Regulators 15 years old or older
should be replaced.
|